- +39 0372 830441
- Mon–Fri 8:30–17:30
Only certified materials are used for the pressure vessel, and non-destructive testing (NDT) – radiographic testing of the intersection and butt welds, dye penetrant testing of the fillet welds – is carried out by our qualified technician and verified by a Notified Body. The boiler is CE marked in accordance with the Pressure Equipment Directive (PED) 2014/68/EU (UKCA marking available on request) and fitted with a full set of safety devices.
The tube plates are drilled cold by hand to preserve all the physical properties of the material, and can be either flat and fillet welded or fully hot-flanged to absorb thermal expansion at varying loads. All joints are carefully welded using manual/automatic procedures.
The external surfaces and headers are insulated with high-density mineral wool (rock wool) (100 kg/m³, clad in aluminium or stainless steel) and finished with special paints to minimise heat losses.
Our steam boiler is designed for high performance and energy savings. With a generous heating surface and a large steam space, it maintains high efficiency even under heavy duty and delivers high quality dry steam. Fitted with low NOx burners and advanced control systems, it meets the most stringent emission regulations. Easy to install and maintain, thanks to its inspection doors and ergonomic control panel, the boiler offers modular, customisable options to suit all your requirements, including remote monitoring and integrated energy efficiency solutions.
The boiler has a high-quality steel pressure vessel in a horizontal cylindrical design, with a generously sized furnace that ensures complete combustion. Access openings at the top and bottom make inspection easy, and the efficient, fully water-cooled furnace has no refractory. The fire tubes and the front and rear smokeboxes are in carbon steel and designed for easy inspection. High-density mineral wool insulation retains the heat effectively, while a steel base frame supports the boiler and its ancillaries.
Valves
Main steam stop valve
Blowdown valve with isolating valve
Control and regulating equipment
Steam pressure gauge with three-way gauge cock and test flange
Operating pressure switches (two-stage burner) / pressure transmitter for burner modulation (modulating burner)
2 × water level gauges (gauge glasses), each with 2 × isolating cocks (the lower one is a three-way cock for draining and blowdown)
Safety devices
High-pressure limiter (manual reset)
2 × safety valves
Control panel
Painted steel enclosure, IP54-rated
Door-interlocked main isolator
Burner on/off switch
Feedwater pump on/off switch
Auxiliary circuit transformer
Fuses
Indicator lights
Feedwater system, comprising:
Isolating valve fitted directly to the boiler shell
Non-return valve connected to the isolating valve
Skid-mounted electric feedwater pump with 1 × isolating valve and 1 × non-return valve. The pump is supplied pre-wired and pre-piped on the skid. Flow rate and head comply with all current regulations.
Our 24 h unattended operation kit (up to 24 hours between operator checks) includes, in addition to the standard equipment, the following components:
Our 72 h unattended operation kit (up to 72 hours between operator checks, in line with BG01) includes, in addition to the standard equipment, the following components: