SRH

Once-through (forced circulation) steam generator in which the water is pumped by one or more feedwater pumps through a single tube, the coil, which forms the heating surface.

The SRH is a horizontal packaged unit, pressurised, with a three-pass design, in which the tube bundle (coil) is wound in a continuous spiral. The first gas pass takes place in the combustion chamber and the other two between the coils.

The whole unit is CE marked in accordance with the Pressure Equipment Directive (PED) 2014/68/EU (UKCA marking available on request) and fitted with all the required safety devices. All joints are carefully welded using manual / automatic processes.

On request, the outer surfaces and headers are insulated with high-density mineral wool (rock wool, 100 kg/m³), clad in aluminium or stainless steel. It is often paired with a steam accumulator.

Caldaie Melgari: pioneers in sustainable heat

The SRH steam generator is always supplied with an inverter-driven feedwater pump, for precise control of the water flow rate and optimum steam dryness.

Steam output: from 100 kg/h to 4,000 kg/h (F&A 100 °C)

Efficiency: the flue gas velocity in the coil is so high that no soot can build up, so efficiency remains constant at over 90% (net CV).

Pressure: 12 to 30 bar g

Fuel: designed to fire both liquid and gaseous fuels. As well as the standard fuels (natural gas, LPG, gas oil), firing on biogas, biomethane, kerosene or heavy fuel oil (HFO) is available on request.

THE KEY BENEFITS FOR YOU

The SRH steam generator is the ideal solution for anyone looking for reliability, efficiency and safety. Thanks to its advanced technology, the generator reaches operating conditions within minutes, saving time and resources. The compact design and low water content significantly reduce the risk of explosion, for maximum operational safety. Maintenance is quick and easy thanks to the fully opening doors, while low NOx emissions ensure compliance with the most stringent environmental regulations. With the SRH steam generator you get not only excellent performance but also a reduced environmental impact, making your business more competitive and sustainable.
Technical diagram of the SRH horizontal compact steam boiler with numbered components

THE BOILER BODY

The body of the SRH is designed for strength and durability while maintaining high thermal efficiency. Made of carbon steel plate of suitable thickness, the cylindrical shell is built to withstand the highest pressures, with reinforced end plates and the option of a custom flue connection. The internal coil, wound in a continuous spiral, ensures effective heat distribution, while the easily removable front and rear doors allow straightforward inspection and maintenance. Every detail of the boiler body is engineered for superior performance, safety and a long working life, making the SRH the best choice for those who accept no compromises.

Steam output FOR all sizes

ANCILLARY EQUIPMENT

  1. Valves
    • Main steam stop valve
    • Start-up / blowdown valve
    • Non-return valve for the feedwater system
    • Three-way valve with cock and test flange

 

  1. Controls and instrumentation
    • Steam pressure gauge
    • Control pressure switches (two-stage burner) / pressure sensor for burner modulation (modulating burner)
    • Glycerine-filled three-colour pressure gauge with pressure switch
    • Electronic steam pressure indicator
    • Flow switch

 

  1. Safety devices
    • High-pressure limiter (manual reset)
    • High-pressure steam safety valve
    • Water-side high-pressure safety switch (coil blockage protection)
    • High flue gas temperature safety thermostat
    • Steam temperature safety thermostat

 

  1. Control panel
    • Painted steel enclosure, IP54 rated
    • Main isolator with door interlock
    • Burner on/off switch
    • Pump on/off switch
    • Transformer for auxiliaries
    • Fuses
    • Indicator lights

Feedwater system comprising the following components

One or more high-pressure positive displacement pumps (inverter-driven), triple-piston with ceramic cylinders, complete with self-cooled electric motor and direct motor / pump coupling with safety guard.

YOU MAY ALSO BE INTERESTED IN

Get in touch

Our team of experts is always on hand to help you

ALL THE BENEFITS

  • The advantage of the SRH steam generator is that it reaches the required operating conditions within minutes, in complete safety. Its low water content also protects your boiler, in particular against the risk of water-side explosion.
  • The generous heating surface keeps specific heat flux low and ensures high efficiency even in continuous, high-demand operation.
  • The horizontal design makes the SRH generator easy to maintain and clean. The front and rear doors also open fully for cleaning and/or withdrawal of the coil on purpose-built guide rails.
  • The SRH generator is characterised by low NOx emissions (always below 80 mg/Nm³; under optimum conditions, around 55 mg/Nm³). The SRH therefore complies with the most stringent national and EU NOx and CO emission limits. It can be paired with low NOx gas burners, delivering optimum environmental performance right from the lowest outputs available.
  • The control panel, positioned at a convenient working height, gives easy access to all the boiler’s control systems.
  • The boiler is delivered ready for connection to the fuel supply, power supply, drains and water circuits, making installation quick and simple.
  • On request, we can offer integrated solutions to improve boiler efficiency and save fuel – for example an economiser, a heat exchanger that recovers residual heat from the flue gases to preheat the feedwater before it enters the boiler, saving energy and reducing fuel consumption.
  • Fully modulating control of the burner and feedwater pump, managed by PLC (Programmable Logic Controller) and inverter, is available as an option.
  • The boiler is supplied either skid-mounted on a heavy-duty base frame for immediate installation, or containerised together with the other boiler house equipment (e.g. water treatment system, deaerator, removable blowdown vessel, etc.).
  • On request, the boiler can be equipped for unattended operation – 24 h / 72 h between operator checks, in line with BG01 – with high-integrity self-monitoring low-water level limiters, a self-monitoring high-water level limiter, a boiler water TDS controller with probe, a feedwater conductivity controller with probe, a TDS blowdown valve and an automatic bottom blowdown valve.
  • On request, we can provide support during assembly, installation and commissioning, as well as a spares and emergency service with 24-hour call-out.
  • The boiler can be configured to your exact requirements: a wide range of optional ancillaries is available to tailor the product to any specific request.

THE BOILER BODY

  • Cylindrical casing in carbon steel plate of suitable thickness, housing the pressure vessel, with suitably reinforced end plates and, on request, a circular flue connection (variant on the standard version).
  • Pressure vessel consisting of a single or twin coil of increasing cross-section, made up of an outer economiser coil bank and an inner evaporator coil bank wound in a continuous spiral.
  • Internal rear baffle in high-temperature steel, lined with refractory castable to seal the flue gases between the first and second pass.
  • Hinged, bolted front door with flame sight glass and burner mounting plate, lined with refractory and insulating castable to seal the flue gases between the second and third pass. The door is also easily removable, making inspection and cleaning easier and allowing the coil to be withdrawn as a single unit if required.
  • Hinged, bolted outer rear door with circular flue connection, lined with insulating castable.
  • Steel base frame for mounting the boiler and its ancillaries.

Download the technical datasheet