SRV

Once-through (forced circulation) steam generator in which the water is pumped by one or more feedwater pumps through a single tube, the coil, which forms the heating surface.

The SRV is a vertical packaged unit, pressurised, with a three-pass design, in which the tube bundle (coil) is wound in a continuous spiral. The first gas pass takes place in the combustion chamber and the other two between the coils. 

The whole unit is CE marked in accordance with the Pressure Equipment Directive (PED) 2014/68/EU (UKCA marking available on request) and fitted with all the required safety devices. All joints are carefully welded using manual / automatic processes.

On request, the outer surfaces and headers are insulated with high-density mineral wool (rock wool), clad in aluminium or stainless steel. It is often paired with a steam accumulator.

Caldaie Melgari: pioneers in sustainable heat

The SRV steam generator is always supplied with an inverter-driven feedwater pump, for precise control of the water flow rate and optimum steam dryness.

Steam output: from 100 kg/h to 4,000 kg/h (F&A 100 °C)

Efficiency: the flue gas velocity in the coil is so high that no soot can build up, so efficiency remains constant at over 90% (net CV).

Pressure: 12 to 30 bar g

Fuel: designed to fire both liquid and gaseous fuels. As well as the standard fuels (natural gas, LPG, gas oil), firing on biogas, biomethane, kerosene or heavy fuel oil (HFO) is available on request.

THE KEY BENEFITS FOR YOU

Our SRV steam generator is the ideal solution for anyone looking for high performance and maximum safety. It reaches operating conditions very quickly, giving a fast, safe start-up and, thanks to its low water content, a minimal risk of explosion. Its generous heating surface keeps efficiency high even in continuous operation, holding running costs down. The compact, versatile vertical design makes it easy to install anywhere, making it the perfect choice for companies that need a reliable steam generator, compliant with the most stringent emissions regulations and fitted with an easy-to-use control panel. Configurable with a wide range of ancillaries, the SRV meets every specific requirement with integrated solutions for energy saving and operating efficiency.

Technical diagram of the SRV vertical compact steam boiler with numbered components

THE BOILER BODY

The pressure vessel of the SRV steam generator is designed for strength and a long service life. Made of thick carbon steel plate, it withstands high pressures and effectively protects the heart of the generator. The design features a single or twin coil wound in a continuous spiral, which optimises heat distribution and improves energy efficiency. The internal rear steel plug, lined with refractory cement, provides a perfect gas seal between the passes, preventing leakage and ensuring safe, reliable operation. The whole unit is mounted on a steel base frame designed to carry the weight of the boiler and its ancillaries, making installation and maintenance easier. With the SRV, you are investing in advanced technology that delivers superior performance and a long working life.

Steam output FOR all sizes

ANCILLARY EQUIPMENT

  1. Valves
    • Main steam stop valve
    • Start-up / blowdown valve
    • Non-return valve for the feedwater system
    • Three-way valve with cock and test flange
  2. Controls and instrumentation
    • Steam pressure gauge
    • Control pressure switches (two-stage burner) / pressure sensor for burner modulation (modulating burner)
    • Glycerine-filled three-colour pressure gauge with pressure switch
    • Electronic steam pressure indicator
    • Flow switch
  3. Safety devices
    • High-pressure limiter (manual reset)
    • High-pressure steam safety valve
    • Water-side high-pressure safety switch (coil blockage protection)
    • High flue gas temperature safety thermostat
    • Steam temperature safety thermostat
  4. Control panel
    • Painted steel enclosure, IP54 rated
    • Main isolator with door interlock
    • Burner on/off switch
    • Pump on/off switch
    • Transformer for auxiliaries
    • Fuses
    • Indicator lights

Feedwater system comprising the following components

One or more high-pressure positive displacement pumps (inverter-driven), triple-piston with ceramic cylinders, complete with self-cooled electric motor and direct motor / pump coupling with safety guard.

YOU MAY ALSO BE INTERESTED IN

Get in touch

Our team of experts is always on hand to help you

ALL THE BENEFITS

  • The advantage of the SRV steam generator is that it reaches the required operating conditions within minutes, in complete safety – particularly with regard to the risk of water-side explosion.
  • The generous heating surface keeps specific heat flux low and ensures high efficiency even in continuous, high-demand operation.
  • The SRV generator is easy to site thanks to its small footprint: the vertical design makes it suitable for any type of plant room.
  • The SRV generator is characterised by low NOx emissions (always below 80 mg/Nm³; under optimum conditions, around 55 mg/Nm³). The SRV therefore complies with the most stringent national and EU NOx and CO emission limits. It can be paired with low NOx gas burners, delivering optimum environmental performance right from the lowest outputs available.
  • The control panel, positioned at a convenient working height, gives easy access to all the boiler’s control systems.
  • The boiler is delivered ready for connection to the fuel supply, power supply, drains and water circuits, making installation quick and simple.
  • On request, we can offer integrated solutions to improve boiler efficiency and save fuel – for example an economiser, a heat exchanger that recovers residual heat from the flue gases to preheat the feedwater before it enters the boiler, saving energy and reducing fuel consumption.
  • Fully modulating control of the burner and feedwater pump, managed by PLC (Programmable Logic Controller) and inverter, is available as an option.
  • The boiler can be skid-mounted on a heavy-duty base frame for immediate installation together with the other boiler house equipment (e.g. water treatment system, deaerator, removable blowdown vessel, etc.).
  • On request, the SRV can be equipped for operation without continuous operator attendance for up to 30 working days, using our dedicated kit (e.g. high-integrity self-monitoring low-water level limiters, self-monitoring high-water level limiter, boiler water TDS controller with probe, feedwater conductivity controller with probe, TDS blowdown valve and automatic bottom blowdown valve).
  • On request, we provide support during assembly, installation and commissioning, as well as a spares and emergency service with 24-hour call-out.
  • The boiler can be configured to your exact requirements: a wide range of optional ancillaries is available to tailor the product to any specific request.

THE BOILER BODY

  • Cylindrical casing in carbon steel plate of suitable thickness, housing the pressure vessel, with suitably reinforced end plates and, on request, a circular flue connection (variant on the standard version).
  • Pressure vessel consisting of a single or twin coil of increasing cross-section, made up of an outer economiser coil bank and an inner evaporator coil bank wound in a continuous spiral.
  • Internal rear baffle in high-temperature steel, lined with refractory castable to seal the flue gases between the first and second pass.
  • Steel base frame for mounting the boiler and its ancillaries.

Download the technical datasheet